Accession Number : ADA330978

Title :   Chilled Water Study EEAP Program for Walter Reed Army Medical Center: Book 2.

Descriptive Note : Final rept.,

Corporate Author : ENTECH ENGINEERING INC READING PA

PDF Url : ADA330978

Report Date : FEB 1996

Pagination or Media Count : 273

Abstract : The Energy Engineering Analysis Program (EEAP) Study for Walter Reed Army Medical Center (WRAMC) was to provide a thorough examination of the central chilled water plants on site. WRAMC is comprised of seventy-one (71) buildings located on a 113-acre site in Washington, D.C. There are two (2) central chilled water plants (Buildings 48 and 49) each with a primary chilled water distribution system. In addition to the two (2) central plants, three (3) buildings utilize their own independent chillers. Two (2) of the independent chillers (Buildings 7 and T-2), one of which is inoperative (T-2), are smaller air-cooled units, while the third (Building 54) has a 1,900-ton chilled water plant comprised of three (3) centrifugal chillers. Of the two (2) central chilled water plants, Building 48 houses six (6) chillers totalling 7,080 tons of cooling and Building 49 houses one (1) chiller with 660 tons of cooling. The total chiller cooling capacity available on site is 9,840 tons. The chilled water systems were reviewed for alternative ways of conserving energy on site and reducing the peak-cooling load. Distribution systems were reviewed to determine which buildings were served by each of the chilled water plants and to determine chilled water usage on site. Evaluations were made of building exterior and interior composition in order to estimate cooling loads. Interviews with site personnel helped Entech better understand the chilled water plants, the distribution systems, and how each system was utilized.

Descriptors :   *ARMY FACILITIES, *WATER CONSERVATION, *WATER ANALYSIS, DISTRIBUTION, ENERGY, LIFE CYCLE COSTS, COOLING AND VENTILATING EQUIPMENT, ENERGY CONSERVATION, SAVINGS, ENERGY CONSUMPTION, COLLECTING METHODS, WATER DISTRIBUTION, AIR COOLED.

Subject Categories : Non-electrical Energy Conversion
      Logistics, Military Facilities and Supplies
      Air Condition, Heating, Lighting & Ventilating

Distribution Statement : APPROVED FOR PUBLIC RELEASE